📄 MOV (INCH)

MOV (INCH)

  MOV in close condition

  MOV in open condition

    Blinking, MOV in trip condition

    Blinking, Open or close permission not received

   Blinking, Trip condition ok, open/close condition ok, ready to run, no open or closed feedback are available

    Blinking, MOV opening

   Blinking, MOV closing

Upon selecting the block icon of the MOV, the corresponding faceplate beneath will be unveiled.

Oper: Face plate for operator level control
​Operating Mode:
​AUTO: For auto operation
​MAN: For manual operation, after selecting MAN operator can operate the MOV
​Command:
​OPEN: If Operation Mode is MAN, then press OPEN button and within 10 seconds press INCH button to open the valve
​CLOSE: If Operation Mode is MAN, then press CLOSE button and within 10 seconds press INCH button to close the valve
​INCH : When OPEN or CLOSE button pressed then press INCH button then opening or closing command will start
​Feedbacks:
​If open permission is ok then PERM OPEN else PERM OPEN 
​close permission is ok then PERM CLOSE else PERM CLOSE
​​​If interlock condition is ok then ​​INTERLOCK else INTERLOCK 
MOV BLOCK ICON: MOV block icon with Tag No.
​Valve Status: MOV status is showing

Basic: Face plate for operator level control
​​Feedback:
​​Operating Mode:  MANUAL/AUTO 
​Valve Status: OPENED/CLOSED
​Torque Status: If ok then OK else OK 
​Trip FeedBack: ​If of then TRIP_FB else TRIP_FB 
​Run FeedBack: If ok then RUN_FB else RUN_FB  
​Operational Summary:
​OPENED TIME (hr): MOV total opened time in hour
​CLOSED TIME (hr): MOV total closed time in hour

Advanced: Faceplate for manager level
​Valve Control Parameters:
​Run FeedBack Time (sec): Run Feedback receiving time
​​ZS FeedBack Time (sec): Open or close feedback receiving time
​​Operational Summary:
​OPENED TIME (hr): MOV total opened time
​CLOSED TIME (hr): MOV total closed time
​OPEN COUNT: MOV total opened count
​CLOSE COUNT: MOV total closed count

DIAG: Faceplate for manager level
​Diagnostic Parameters:
​Feedback Fault: If any fault signal is available then FB_Fault else FB_Fault 
​​Interlock: Interlock No interlock
​     Interlock ​Interlock available
​Permission Open: PERM OPEN open permission is satisfied
​       ​ ​PERM OPEN open permission is not satisfied
​Permission Close: PERM CLOSE close permission is satisfied
​        PERM CLOSE close permission is not satisfied
​Trip Feedback: Trip_FB if trip signal received
​   Trip_FB if trip signal OK
​TSO: TSO torque open limit ok
​        TSO torque open limit not ok
​TSC: TSC torque close limit ok
​        TSC torque close limit not ok​
​Valve Closed​​​: ZSC Closed feedback received
ZSC Closed feedback not received
​Valve Opened: ZSO Open feedback received
​   ZSO Open feedback not received